To choose the correct JBD Smart BMS, please confirm the following key parameters:
⚠️ Important:
BMS current is selected based on load power, not battery capacity (Ah).
👉 If you are not sure, please contact us with your battery details. Our team will recommend the correct model for your system.
This is usually related to cell capacity or internal resistance differences.
Suggestions:
Note: The BMS only monitors cell voltage; it does not actively change battery voltage.
Please check the following:
Possible causes:
Possible reasons:
Balancing starts only when the cell reaches the balance voltage:
When a cell reaches the balancing voltage:
This may happen because:
Overcurrent protection is typically set at 2–3 times the rated continuous current. It triggers only when the current exceeds the threshold within ~200 ms.
If current exceeds the rated value but does not reach the protection threshold, the BMS may overheat and get damaged.
Overcurrent protection is designed to protect against abnormal conditions such as:
It is not designed for current limiting during normal operation.
It is not recommended to set it too low.
Minimum should not be below 0.02V.
Default value 0.03V is recommended.
Charging balancing:
Active only during charging. Balancing starts when cells reach the set voltage and the voltage difference between highest and lowest cells reaches the configured threshold.
Static balancing:
Works when there is no charging current. Balancing starts when cells reach the set voltage and the voltage difference threshold is met.